Rockwell Automation 1785 PLC-5 User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
Hardware Components
I/O Status File 1-31
Word 2 in the I/O Status File
This bit: Corresponds to:
Inhibit bits 00 first 1/4 rack starting I/O group 0
01 second 1/4 rack starting I/O group 2
02 third 1/4 rack starting I/O group 4
03 fourth1/4 rack starting I/O group 6
Reset bits 08 first 1/4 rack starting I/O group 0
09 second 1/4 rack starting I/O group 2
10 third 1/4 rack starting I/O group 4
11 fourth1/4 rack starting I/O group 6
ATTENTION: When you use a ladder program or the software to inhibit and reset an I/O rack, you must set or
clear the reset and inhibit bits that correspond to each quarter rack in a given chassis. Failure to set all the appropriate
bits could cause unpredictable operation due to scanning only part of the I/O chassis.
00010203040506070809101112131415
Not Used
Not Used
Inhibit Bits
Reset Bits
N15:15
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 171 172

Comments to this Manuals

No comments