Troubleshooting
Extended Local I/O 5-31
Troubleshooting
Extended Local I/O 5-31
Off On RPLC Fatal Power On Self Test failure RAM or FLASH test failed.Processor
fault or watchdog time-out.
Contact Rockwell Automation for
service
None Hardware fault Defective hardware
Blinking Off INIT Requires ControlNet configuration No communication with ControlNet
Configuration Manager node
Verify Configuration Manager node is
operating
IDLE Processor not actively controlling I/O Adapter not mapped Verify mapping of adapter in
processor
NET
ERR
Network error Cable error or no other nodes on
network
Verify network cabling
On Off RUN Normal indication - processor is in
RUN mode
None None
PRGM Normal indication - processor is in
program or test mode
None None
Blinking in unison CODE
UPDT
Firmware update mode Adapter firmware is being updated via
A-B Flash Update Utility
None
Blinking alternately BOOT Running boot code Adapter has corrupted firmware Update adapter firmware with A-B
Flash Update Utility
OK
Indicator
Display
Mnemonic
Description Probable Cause Recommended Action
Green Red
ControlNet I/O Status