Instruction Set
Diagnostic 3-30
Diagnostic Instructions
Instruction Description
File Bit Compare
FBC
Status Bits:
EN - Enable
DN - Done Bit
ER - Error Bit
IN - Inhibit Bit
FD - Found Bit
When the input conditions go from false-to-true, the processor compares the number of bits
specified in the Cmp Control Length (48) of the Source file (#I:031) with the bits in the Reference
file (#B3:1). The processor stores the results (mismatched bit numbers) in the Result file
(#N7:0). File R6:4 controls the compare and file R6:5 controls the file that contains the results.
The file containing the results can hold up to 10 (the number specified in the Length field)
mismatches between the compared files.
FILE BIT COMPARE
Source #I:031
Reference #B3:1
Result #N7:0
Cmp Control R6:4
Length 48
Position 0
Result Control R6:5
Length 10
Position 0
FBC