Rockwell Automation 1785 PLC-5 User Manual Page 21

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 20
Hardware Components
Processor Status File 1-17
processor status file continued...
This word of the status file: Stores:
S:11 Major fault
Bit Description
0 corrupted program file (codes 10-19)
1 corrupted address in ladder file (codes 20-29)
2 programming error (codes 30-49)
3 SFC fault (codes 71-79)
4 error while assembling program (code 70); duplicate LBLs found
5 start-up protection fault; processor sets this bit when powering up in run mode if bit S:26/1 is
set
6 peripheral device fault
7 jumped to fault routine (codes 0-9)
8 watchdog faulted
9 system configured wrong (codes 80-89)
10 recoverable hardware error
11 MCP does not exist or is not ladder or SFC file
12 PII does not exist or is not ladder
13 STI does not exist or is not ladder
14 fault routine does not exist or is not ladder
15 fault occurred in a non-ladder file
Page view 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 171 172

Comments to this Manuals