Rockwell Automation 1785 PLC-5 User Manual Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
Hardware Components
Processor Status File 1-23
processor status file continued...
This word of the status file: Stores:
S:17 Minor fault (word 2)
Bit Description
0 BT queue full to remote I/O
1 queue full – channel 1A; maximum remote block transfers used
2 queue full – channel 1B; maximum remote block transfers used
3 queue full – channel 2A; maximum remote block transfers used
4 queue full – channel 2B; maximum remote block transfers used
5 no modem on serial port
6 remote I/O rack in local rack table; or, remote I/O rack is greater than the image size
7 firmware revision for channel pairs 1A/1B or 2A/2B does not
match processor firmware revision
8 ASCII instruction error
9 duplicate node address
10 DF1 master poll list error
11 protected processor data table element violation
12 protected processor file violation
13 using all 32 ControlNet MSGs
14 using all 32 ControlNet 1771 READ and/or 1771 WRITE CIOs
15 using all 8 ControlNet Flex I/O CIOs
See also S:10.
S:18 Processor clock year
S:19 Processor clock month
S:20 Processor clock day
S:21 Processor clock hour
S:22 Processor clock minute
S:23 Processor clock second