Troubleshooting
Scanner Mode 5-15
Classic PLC-5
processors only
Troubleshooting – Classic PLC-5 Processors (except PLC-5/10 and PLC-5/12) in Scanner Mode
Indicator Color Description Probable Cause Recommended Action
REM I/O green
(steady)
active remote I/O link normal operation none
red
(steady)
remote I/O link fault wiring, adapter
module(s)
Check all connections, check adapter
module(s)
If you have 6200 Series Software, put the
processor in PROG mode and do an auto
configure for remote racks (see your 6200
Series Software documentation)
green/red
(blinking)
partial remote I/O link fault one or more
remote I/O
chassis faulted
Check status bits in I/O status file (element #7)
to identify faulted chassis number; check
wiring, adapter module(s), power supplies
If you have 6200 Series Software, put the
processor in PROG mode and do an auto
configure for remote racks (see your 6200
Series Software documentation)
off no remote I/O selected none