Hardware Components
Processor Status File 1-15
processor status file continued
This word of the status file: Stores:
S:7 Global status bits:
S:7/0-7 - - rack fault bits for racks 0-7
S:7/8-15 - - rack queue-full bits for racks 0-7
See also S:27, S:32, S:33, S:34, and S:35
S:8 Last program scan (in ms)
S:9 Maximum program scan (in ms)
S:2 Switch setting information
bits 0 - 6 DH+ station number
bit 11-12 are set based on the I/O chassis backplane switches
bit 12
bit 11 = I/O chassis addressing
0 0 illegal
1 01/2-slot
0 11-slot
1 12-slot
bit 13: 1 = load from EEPROM
bit 14: 1 = RAM backup not configured
bit 15: 1 = memory unprotected
S:3 to S:6 Active Node table for channel 1A
Word Bits DH+ Station #
3 0-15 00-17
4 0-15 20-37
5 0-15 40-57
6 0-15 60-77