Rockwell Automation 1785 PLC-5 User Manual Page 133

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 132
Troubleshooting
General Problems 5-13
Classic PLC-5
processors only
Indicator Color Description Probable Cause Recommended Action
PROC
REM I/O
COMM
all red
(steady)
internal diagnostics have
failed
Power down, reseat processor and power up.
Then, clear memory and reload your program.
Replace EEPROM with new program. Then, if
necessary, replace
the processor.
FORCE amber
(steady)
forces enabled normal operation none
amber
(blinking)
forces present, but not
enabled
normal operation none
off no forces present normal operation none
BATT off battery is good normal operation none
red
(steady)
battery low Replace battery within 1-2 days (typical).
ADPT green
(steady)
processor is in adapter
mode
normal operation none
off processor is in scanner
mode
normal operation none
COMM
BATT
FAULT
REM I/O PROC
ACTIVE
RUN
ADPT FORCE
REM
R
U
N
P
R
O
G
Page view 132
1 2 ... 128 129 130 131 132 133 134 135 136 137 138 ... 171 172

Comments to this Manuals