6–18 Parameters
Publication 1336 FORCE–5.18 ––March, 1999
339
Analog Input 1
[Analog In 1]
Analog In 1 displays the result of converting a ±10V
signal to a ±32767 value using Analog In 1 Scale
(parameter 393) and Analog In 1 Offset (parameter
392). You can link this digital value to other 1336
FORCE parameters.
Parameter Number 339
Parameter Type Read Only, Source
Display Units / Drive Units None
Factory Default 0
Minimum Value –32767
Maximum Value +32767
File – Group Communications I/O – Analog Input
340
Analog Input 2
[Analog In 2]
Analog In 2 displays the result of converting a ±10V
signal to a ±32767 value using Analog In 2 Scale
(parameter 395) and Analog In 2 Offset (parameter
394). You can link this digital value to other 1336
FORCE parameters.
Parameter Number 340
Parameter Type Read Only, Source
Display Units / Drive Units None
Factory Default 0
Minimum Value –32767
Maximum Value +32767
File – Group Communications I/O – Analog Input
341
Analog Input 3
[Analog In 3]
Analog In 3 displays the result of converting a ±10V
signal to a ±32767 value using Analog In 3 Scale
(parameter 397) and Analog In 3 Offset (parameter
396). You can link this digital value to other 1336
FORCE parameters.
Parameter Number 341
Parameter Type Read Only, Source
Display Units / Drive Units None
Factory Default 0
Minimum Value –32767
Maximum Value +32767
File – Group Communications I/O – Analog Input
342
Analog Input 4
[Analog In 4]
Analog In 4 displays the result of converting a ±10V
signal to a ±32767 value using Analog In 4 Scale
(parameter 399) and Analog In 4 Offset (parameter
398). You can link this digital value to other 1336
FORCE parameters.
Parameter Number 342
Parameter Type Read Only, Source
Display Units / Drive Units None
Factory Default 0
Minimum Value –32767
Maximum Value +32767
File – Group Communications I/O – Analog Input
Page view 159