2–4 Starting Up
Publication 1336 FORCE–5.18 ––March, 1999
Before you can transfer data between the ControlNet Adapter Board
and the analog I/O, you need to do the following:
1. Hard wire the analog I/O to the CNA Board terminals.
2. Set up the analog input and output configuration parameters in
the drive.
3. Create any user links, if appropriate.
Note: The ControlNet Adapter Board has been pre-configured for
your convenience. The pre-configured links are listed later in Figure
2.4.
Each terminal has parameters associated with it as shown here in the
analog I/O block diagram.
+10V REF 17
REF COM 18
–10V REF 19
OUT1 1 Par 401 Scale
COM1 2 Par 400 Offset
TB21
Analog Out #1 Analog Out 1
OUT2 3 Par 403 Scale
COM2 4 Par 402 Offset
Analog Out #2 Analog Out 2
OUT3 5 Par 405 Scale
COM3 6 Par 404 Offset
Analog Out #3 Analog Out 3
OUT4 7 Par 407 Scale
COM4 8 Par 406 Offset
Analog Out #4 Analog Out 4
339
IN1+ 9 Par 393 Scale
IN1– 10 Par 392 Offset
Analog In #1 Analog In 1
340
IN2+ 11 Par 395 Scale
IN2– 12 Par 394 Offset
Analog In #2 Analog In 2
341
IN3+ 13 Par 397 Scale
IN3– 14 Par 396 Offset
Analog In #3 Analog In 3
342
IN4+ 15 Par 399 Scale
IN4– 16 Par 398 Offset
Analog In #4 Analog In 4
Power
Supply
387
388
390
389
Setting Up the Analog I/O
"