7–11Troubleshooting
Publication 1336 FORCE–5.18 ––March, 1999
Fault text and
code:
Suggested action:Description:
Fault
type:
No AP LM Exists
25023
Hard
The ControlNet Adapter Board
has detected that a language
module has not been installed
on the ControlNet Adapter
Board.
Reset the drive. If the fault persists,
replace the language module.
SP Pt1 Timeout
26038
Soft,
warning,
or none
The device connected to Port 1
of SCANport has been
disconnected.
Reconnect Device if desired.
SP Pt2 Timeout
26039
Soft,
warning,
or none
The device connected to Port 2
of SCANport has been
disconnected.
Reconnect Device if desired.
SP Pt3 Timeout
26040
Soft,
warning,
or none
The device connected to Port 3
of SCANport has been
disconnected.
Reconnect Device if desired
SP Pt4 Timeout
26041
Soft,
warning,
or none
The device connected to Port 4
of SCANport has been
disconnected.
Reconnect Device if desired.
SP Pt5 Timeout
26042
Soft,
warning,
or none
The device connected to Port 5
of SCANport has been
disconnected.
Reconnect Device if desired.
SP Comm Fault
26043
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
HW Malfunction
34001
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
HW Malfunction
34002
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
HW Malfunction
34003
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
HW Malfunction
34004
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
HW Malfunction
34005
Hard
The integrity check on the board
hardware has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
SW Malfunction
34016
Hard
The integrity check on the board
software has failed.
Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.
Page view 198