6–29Parameters
Publication 1336 FORCE–5.18 ––March, 1999
400
Analog Output 1 Offset
[Analog Out 1 Offset]
Analog Out 1 Offset determines the offset applied to
the Analog Out 1 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number 400
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Output
401
Analog Output 1 Scale
[Analog Out 1 Scale]
Analog Out 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 1 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor Drive Units
1 32767
1/2 16383
1/4 8192
1/16 2048
Parameter Number 401
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –1
Maximum Value +1
File – Group Communication I/O – Analog Output
402
Analog Output 2 Offset
[Analog Out 2 Offset]
Analog Out 2 Offset determines the offset applied to
the Analog Out 2 value after the scale factor is
applied. This allows you to shift the range of the
analog output.
Parameter Number 402
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Output
403
Analog Output 2 Scale
[Analog Out 2 Scale]
Analog Out 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 2 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.
Scale Factor Drive Units
1 32767
1/2 16383
1/4 8192
1/16 2048
Parameter Number 403
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –1
Maximum Value +1
File – Group Communication I/O – Analog Output