6–27Parameters
Publication 1336 FORCE–5.18 ––March, 1999
392
Analog Input 1 Offset
[Analog In 1 Offset]
Analog In 1 Offset determines the offset applied to
the raw Analog In 1 values before the scale factor is
applied. This allows you to shift the range of the
analog input.
Parameter Number 392
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Input
393
Analog Input 1 Scale
[Analog In 1 Scale]
Analog In 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +10V dc signal
applied to Analog In 1 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of ±32767 (16 x 2048). The
absolute digital value is clamped at 32767.
Scale Factor Drive Units
1 2048
2 4096
4 8192
16 32767
Parameter Number 393
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –16
Maximum Value +16
File – Group Communications I/O – Analog Input
394
Analog Input 2 Offset
[Analog In 2 Offset]
Analog In 2 Offset determines the offset applied to
the raw Analog In 2 values before the scale factor is
applied. This allows you to shift the range of the
analog input.
Parameter Number 394
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±4096
Factory Default 0
Minimum Value –20 Volts
Maximum Value +20 Volts
File – Group Communications I/O – Analog Input
395
Analog Input 2 Scale
[Analog In 2 Scale]
Analog In 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +10V dc signal
applied to Analog In 2 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of ±32767 (16 x 2048). The
absolute digital value is clamped at 32767.
Scale Factor Drive Units
1 2048
2 4096
4 8192
16 32767
Parameter Number 395
Parameter Type Read/Write, Non–Linkable Sink
Display Units / Drive Units ±32767
Factory Default +1
Minimum Value –16
Maximum Value +16
File – Group Communications I/O – Analog Input
Comments to this Manuals