148 Rockwell Automation Publication 2099-UM001D-EN-P - December 2012
Chapter 6 Troubleshoot the Kinetix 7000 Drive System
AuxFeedbackFault
(Aux Fdbk AQB)
E61 Auxiliary encoder has encountered an illegal state transition. DISABLE DRIVE No
AuxFeedbackFault
(Aux Fdbk Loss)
E62 The feedback wiring is open, shorted or missing. DISABLE DRIVE No
AuxFeedbackNoise
(Aux Fdbk Noise)
E63 Presence of noise on auxiliary feedback cable.
DISABLE DRIVE /
Feedback Noise
Yes
MotorFeedbackNoise
(Mtr Fdbk Noise)
E64 Presence of noise on motor feedback cable.
No Fault Message
(condition indicated by on-
screen message)
(Hookup Fault)
E65 Hookup procedure failed. DISABLE DRIVE No
No Fault Message
(condition indicated by on-
screen message)
(Atune Flt)
E66 Autotune procedure failed. DISABLE DRIVE No
DriveHardFault
(Task Init)
E67 Operating system failed. SHUTDOWN No
DriveHardFault
(SCANport Comm)
E68 DPI communication failed. STOP MOTION No
DriveHardFault
(Objects Init)
E69 Nonvolatile memory attribute out of range. SHUTDOWN No
DriveHardFault
(NV Mem Init)
E70 Nonvolatile memory corrupted. SHUTDOWN No
DriveHardFault
(Memory Init)
E71 RAM or flash memory validation failure. SHUTDOWN No
DriveOvertempFault
(Drive Overtemp)
E72
Inverter temperature limit exceeded. Firmware I
2
t protection does not generate a fault,
rather it dynamically folds back current when 110% of drive rating is reached.
SHUTDOWN Yes
DriveHardFault
(Can Init)
E76 Either DPI or backplane CAN initialization failure. SHUTDOWN No
DriveHardFault
SERCOS Init
E78 Control hardware fault detected. SHUTDOWN No
HardwareFault
(CPLD FLT)
E80 Control hardware fault detected. SHUTDOWN No
IGBTTempFault
(IGBTFLT)
E109 Junction temperature of IGBT exceeded. SHUTDOWN No
EEPROMFault
(CPLD FLT)
E110 EEPROM failure. EEPROM data corrupt or bus not calibrated. SHUTDOWN No
RegenPSOK
(CPLD FLT)
E111 Regenerative PS+/- missing at GPIO. SHUTDOWN No
All Others RESERVED
(1) The Logix Motor Thermal Fault Action is tied to the motor thermostat fault. If this is set to Shutdown or Disable (in Logix), the drive will fold back the current when the I
2
T calculation indicates that the
motor temperature has exceeded 10% of its rated temperature. If it is set to Stop Motion or Status Only, the drive will not fold back the current. The I
2
T calculation never generates a fault.
Logix Fault Message
(HIM)
Error
Code
Description Drive Fault Action/
Attribute
RSLogix
Programmable
Fault Action?