Rockwell Automation Publication 2099-UM001D-EN-P - December 2012 19
Start Chapter 1
CE Requirements - System without LIM
To meet CE requirements when your Kinetix 7000 system does not use a 2094
line interface module to supply AC line and dc control power, the following
requirements apply:
Install an 8720MC-RF180 line filter as close to the 8720MC-RPS unit as
possible, and the AC line filter (2090-XXLF-TCxxxx) as close to the
Kinetix 7000 drive as possible.
For MPx motors, use 2090 series motor power cables or use connector kits.
Terminate cable shields at the chassis and the motor terminal block with a
360° connection.
For HPK-Series motors, use UL Approved 4 wire, 600V AC, shield, VFD
cabling. Terminate cable shields at the chassis and the motor with a 360°
connection.
Combined motor power/feedback cables must not exceed 90 m (295.3 ft).
Use 2090 series motor feedback cables or connector kits and terminate the
feedback shield as shown in Chapter 4 for wiring instructions and
Appendix B for motor feedback connector kit catalog numbers. Drive to
motor feedback cables must not exceed 90 m (295.3 ft).
Install the Kinetix 7000 system inside an enclosure. Run input power
wiring in conduit (grounded to the enclosure) outside of the enclosure.
Separate signal and power cables.
Output power, control (I/O), and signal wiring must be braided, shielded
cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.
All shielded cables should terminate with a properly shielded connector.
See the System Design for Control of Electrical Noise Reference Manual,
publication GMC-RM001
, for information on electrical noise reduction and
grounding practices.